TM200C24R Controller M200 14I/10O relay

Детали

Бренд

  • Описание

    Controller M200 24 IO relay

  • Main
    Range of productEasy Modicon M200
    product or component typeLogic Controller
    [Us] rated supply voltage100...240 V AC
    Discrete I/O number24
    Discrete input numberI2...I5: 4 fast input I0, I1, I6, I7: 4 high speed input I8...I13: 6 regular input
    Discrete output number10 relay
    Discrete input voltage24 V
    discrete input voltage typeDC
    Discrete input current7 mA for input
    Discrete input LogicSink or source (positive/negative) type 1 conforming to IEC 61131-2
    Discrete output voltage24 V DC 220 V AC
    Discrete output current2 A
    Discrete output typeRelay normally open
    Power consumption in VA52…64 VA at 100...240 V AC (with max I/O)
    Complementary
    Maximum number of I/O expansion module4 with 128 discrete output(s) for transistor output 4 with 74 discrete output(s) for relay output
    Supply voltage limits85…264 V
    Network frequency50/60 Hz
    Inrush current50 A
    Voltage state 1 guaranteed>= 15 V for input
    Voltage state 0 guaranteed<= 5 V for input
    Input impedance3.3 kOhm for discrete input
    Response time5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input 100 µs turn-off, I2...I5 terminal(s) for fast input 35 µs turn-on, I2...I5 terminal(s) for fast input 10 ms turn-off, Q0...Q9 terminal(s) for relay output 10 ms turn-on, Q0...Q9 terminal(s) for relay output 100 µs turn-off, I8...I13 terminal(s) for regular input 35 µs turn-on, I8...I13 terminal(s) for regular input
    Configurable filtering time0 ms for input 3 ms for input 12 ms for input
    Output voltage limits30 V DC 250 V AC
    Maximum current per output common4 A at COM 2 4 A at COM 0 4 A at COM 1
    Electrical durability100000 cycles AC-12, 240 V, 480 VA, resistive 100000 cycles DC-12, 24 V, 48 W, resistive
    Switching frequency0.1 Hz with maximum load
    Mechanical durability20000000 cycles for relay output
    Minimum load10 mA at 5 V DC for relay output
    Memory capacity512 byte internal flash for backup of programs
    Data storage equipment32 GB micro SD card (optional)
    Battery typeBR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s)
    Backup time3 years at 25 °C (by interruption of power supply)
    Execution time for 1 KInstruction0.3 ms for event and periodic task
    Execution time per instruction0.2 µs Boolean
    Exct time for event task60 µs response time
    Clock drift<= 90 s/month at 25 °C
    Regulation loopAdjustable PID regulator up to 14 simultaneous loops
    Control signal typeQuadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode) Pulse/direction at 100 kHz for fast input (HSC mode) Single phase at 100 kHz for fast input (HSC mode) CW/CCW at 100 kHz for fast input (HSC mode)
    Counting input number4 fast input (HSC mode) at 100 kHz 32 bits
    Integrated connection typeUSB port with mini B USB 2.0 connector Non isolated serial link serial 1 with terminal block connector and RS485 interface Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface Isolated serial link serial 2 with terminal block connector and RS485 interface
    Transmission rate1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB
    Communication port protocolUSB port: USB SoMachine-Network Non isolated serial link: Modbus master/slave RTU/ASCII or SoMachine-Network
    Local signalling1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED per channel (green) for I/O state
    Electrical connectionMini B USB 2.0 connectorfor a programming terminal removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 4 terminal(s) for connecting the serial link1 removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply
    Maximum cable distance between devicesUnshielded cable: <50 m for input Shielded cable: <10 m for fast input Shielded cable: <10 m for high speed input Unshielded cable: <150 m for output
    InsulationNon-insulated between inputs Between output and internal Logic at 1780 V AC Between output groups at 1780 V AC Between supply and internal Logic at 1780 V AC Between input and internal Logic at 500 V AC Between fast input and internal Logic at 500 V AC Between input groups at 500 V AC
    Sensor power supply24 V DC at 250 mA supplied by the Controller
    markingCE
    Mounting supportTop hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715
    Height90 mm
    Depth70 mm
    Width130 mm
    net weight0.405 kg